[1]李风雷,韩瑞春,程志雯,等.光热光电喷射-直接蒸发复合制冷系统性能[J].华侨大学学报(自然科学版),2017,38(2):189-194.[doi:10.11830/ISSN.1000-5013.201702011]
 LI Fenglei,HAN Ruichun,CHENG Zhiwen,et al.Performance of Solar Ejector and Direct Evaporation Combined Refrigeration System Poweredby Photovoltaic Solar Energy[J].Journal of Huaqiao University(Natural Science),2017,38(2):189-194.[doi:10.11830/ISSN.1000-5013.201702011]
点击复制

光热光电喷射-直接蒸发复合制冷系统性能()
分享到:

《华侨大学学报(自然科学版)》[ISSN:1000-5013/CN:35-1079/N]

卷:
第38卷
期数:
2017年第2期
页码:
189-194
栏目:
出版日期:
2017-03-20

文章信息/Info

Title:
Performance of Solar Ejector and Direct Evaporation Combined Refrigeration System Poweredby Photovoltaic Solar Energy
文章编号:
1000-5013(2017)02-0189-06
作者:
李风雷1 韩瑞春1 程志雯2 马军伟3
1. 太原理工大学 环境科学与工程学院, 山西 太原 030024;2. 山西省地震局, 山西 太原 030024;3. 山西锦兴能源有限公司, 山西 吕梁 033600
Author(s):
LI Fenglei1 HAN Ruichun1 CHENG Zhiwen2 MA Junwei3
1. College of Environmental Science and Engineer, Taiyuan University of Technology, Taiyuan 030024, China; 2. Shanxi Earthquake Administration, Taiyuan 030024, China; 3. Shanxi Jinxing Energy Limited Company, Lüliang 033600, China
关键词:
制冷系统 喷射 蒸发 太阳能 光热光电
Keywords:
refrigeration system injection evaporation solar energy photo thermal photovoltaic
分类号:
TK519
DOI:
10.11830/ISSN.1000-5013.201702011
文献标志码:
A
摘要:
提出一种以R134a为制冷剂的光热光电喷射-直接蒸发复合制冷系统,以新疆喀什地区的气象参数为输入,结合Trnsys软件进行建筑模拟和系统仿真计算,分析夏季连续典型气象日内系统的运行情况及其性能.结果表明:直接蒸发冷却系统系数COPm值最大可以达到15.05;COPm平均值达到12.33;太阳能喷射制冷系统机械COPm最大为4.97;复合系统的综合机械性能系数COPm达到8.52;整个夏季完全用机械压缩制冷系统耗电量为1
Abstract:
This paper proposed a solar ejector and direct evaporation combined refrigeration system powered by photovoltaic solar energy. This system used R134a as refrigerant, input meteorological parameters in Kashgar Area, Xinjiang, and combined Trnsys simulation software for building simulation and simulation computation of the system, then conducted a comprehensive analysis of operation and thermal performance of the system during consecutive typical meteorological days in summer. The result shows that the maximum COPm of the direct evaporation refrigeration system can reach 15.05 with the average COPm 12.33. The maximum mechanical COPm of the ejector refrigeration is 4.97, and the comprehensive COPm is 8.52. Morever, power consumption of the mechanical compression refrigeration system is 162.6 kW·h, and the power consumption of the combined system is 65.4 kW·h in summer.

参考文献/References:

[1] HUANG B J,CHANG J M,PETRENKO V A,et al.Solar ejector cooling system using refrigerant R141b[J].Solar Energy,1998,64(4/5/6):223-226.
[2] 方承超,赵军,徐律,等.利用低焓能的压缩-喷射制冷系统的研究[J].工程热物理学报,1995,16(1):5-8.
[3] SELVARAJU A,MANI A.Experimental investigation on R134a vapour ejector refrigeration system[J].International Journal of Refrigeration,2006,29(7):1160-1166.
[4] 张于峰,李灿华,孙萍,等.新型喷射制冷系统的研究[J].工程热物理学报,1999,20(4):405-409.
[5] 李风雷,任艳玲.典型气象日蓄热型太阳能喷射制冷系统性能分析[J].华侨大学学报(自然科学版),2014(2):185-190.
[6] 郑慧凡,张仙平,范晓伟,等.HFO1234yf太阳能喷射制冷系统在西安地区性能分析[J].化学工程,2015,43(3):18-21.
[7] SOKOLOV M,HERSH GAL D.Optimal coupling and feasibility of a solar powered by year round ejector air conditioner[J].Solar Energy,1993,50(6):507-516.
[8] 田琦.太阳能喷射与压缩一体化制冷系统的研究[D].天津:天津大学,2005:1-6.
[9] 张利贺,范晓伟,郑慧凡.太阳能喷射-压缩复合蓄冷系统热力学性能分析[J].中原工学院学报,2011,22(1):11-14.
[10] 中国建筑科学研究院.公共建筑节能设计标准: GB 50189-2005[S].北京:中国计划出版社,2006:25-27.
[11] HAY J E.Calculation of monthly mean solar radiation for horizontal and inclined surface[J].Solar Energy,1979,23(4):301-307.
[12] 辛军哲,周孝清,何淦明.直接蒸发冷却式空调系统的适用室外气象条件[J].暖通空调,2008,38(1):52-53.

备注/Memo

备注/Memo:
收稿日期: 2016-07-17
通信作者: 李风雷(1967-),男,副教授,博士,主要从事空调制冷新技术,热能利用与节能技术的研究.E-mail:fengleili @126.com.
基金项目: 山西省科技攻关项目(20140313006-6); 国家国际科技合作项目(2013DFA61580); 山西省回国留学人员科研基金资助项目(2016-032)
更新日期/Last Update: 2017-03-20